Online UPS Series
|
| MODEL | PowerAgent 1008 Online LCD (L) | PowerAgent 2016 Online LCD (L) | PowerAgent 3024 Online LCD (L) | ||||
| Back Plan | 4 IEC output | 8 IEC output | 6 IEC outpu | ||||
| CAPACITY | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | ||||
| INPUT | |||||||
| Voltage Range | Low Line Transfer | 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) | |||||
| Low Line Comeback | 175 VAC ± 5 % or 85 VAC ± 5 % | ||||||
| High Line Transfer | 300 VAC ± 5 % or 150 VAC ± 5 % | ||||||
| High Line Comeback | 290 VAC ± 5 % or 145 VAC ± 5 % | ||||||
| Frequency | 40 Hz ~ 70 Hz | ||||||
| Phase | Single phase with ground | ||||||
| Power Factor | ≧ 0.99 @ 220-230 VAC (input voltage) | ||||||
| OUTPUT | |||||||
| Output Voltage (Batt. Mode) | ± 3% | ||||||
| Frequency Range (Synchronized Range) | 47 ~ 53 Hz or 57 ~ 63 Hz | ||||||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz | ||||||
| TCurrent Crest Ratio | 3:1 | ||||||
| Harmonic Distortion | ≦ 3 % THD (Linear Load), ≦ 6 % THD (Non-linear Load) | ≦ 4 % THD (Linear Load) ≦ 7 %THD (Non-linear Load) | |||||
| Transfer Time | AC Mode to Batt. Mode | Zero | |||||
| Inverter to Bypass | 4 ms (Typical) | ||||||
| Waveform (Batt. Mode) | Pure Sinewave | ||||||
| EFFICIENCY | |||||||
| AC Mode | 85% | 88% | |||||
| Battery Mode | 83% | ||||||
| BATTERY | |||||||
| Standard Model | Battery Type | 12 V / 7 Ah | 12 V / 7 Ah | 12 V / 9 Ah | |||
| Numbers | 3 | 6 | 6 | ||||
| Typical Recharge Time | 4 hours recover to 90% capacity | ||||||
| Charging Current (max.) | 1.0 A | ||||||
| Charging Voltage | 41.0 VDC ± 1% | 82.1 VDC ±1% | |||||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | |||||
| Numbers | |||||||
| Charging Current (max.) | 8.0A | ||||||
| Charging Voltage | 41.0 VDC ± 1% | 82.1 VDC ±1% | |||||
| INDICATORS | |||||||
| LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||||
| LED Panel | Sixteen LEDs indicating UPS status, Load level, Battery level, overload, fault, and programmable outlet information | ||||||
| ALARM | |||||||
| Battery Mode | Sounding every 4 seconds | ||||||
| Low Batteryl | Sounding every second | ||||||
| Overload | Sounding twice every second | ||||||
| Fault | Continuously sounding | ||||||
| PHYSICAL | |||||||
| Tower Case | Standard Model | Dimension, D X W X H (mm) | 397 X 145 X 220 | 421 X 190 X 318 | |||
| Net Weight (kgs) | 13 | 26 | 28 | ||||
| Long-run Model | Dimension, D X W X H (mm) | 397 X 145 X 220 | 421 X 190 X 318 | ||||
| Net Weight (kgs) | 7 | 13 | 13 | ||||
| Rack Case | Standard Model | Dimension, D X W X H (mm) | 420x438x88[2U] | 580x438x133[3U] | |||
| Net Weight (kgs) | 16 | 29 | 31 | ||||
| Long-run Model | Dimension, D X W X H (mm) | 420x438x88[2U] | 580x438x133[3U] | ||||
| Net Weight (kgs) | 10 | 17 | 17 | ||||
| ENVIRONMENT | |||||||
| Operation Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | ||||||
| Noise Level | Less than 45dB @ 1 Meter | ||||||
| MANAGEMENT | |||||||
| Smart RS-232/USB | Supports Windows 98/2000/2003/XP/Vista/2008, Windows 7, Linux, and MAC | ||||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||||
| * * Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC. | |||||||
| * L means long-run model | |||||||
| * Product specifications are subject to change without further notice | |||||||